8 Way coaxial surge protection device
KLF-X/8TV
1) Product Description:
KLF Series signal surge protective device is designed, produced and tested according to People's Republic of China's QX10.1,communication YD/T1235.1 and IEC61643 product is control strictly according to ISO9001 quality control.The product is applied to video surveillance systems, matrix BNC connector, Optical BNC interface, the camera BNC interface lightning surge protection. It can effectively prevent overvoltage and over current which are induced by lightning or industrial noise and other factors, and other transient surge voltage on the system or equipment or cause permanent damage or momentarily interruption and other hazards. Apply to lightning surge protection of four channels video BNC interface.Core components are selected international brands, multistage protection, low residual voltage, fast response.With advantage of low-volume design, excellent transmission performance, fast response, large intake capacity and long lifetimeApply to monitor system(such as video matrix switchers, cameras, video surveillance equipment, video distributor, etc),video line surge protection.
2) Technology Parameters:
|
TYPE |
KLF-X/8TV |
|
Operating Voltage (Un) |
5V |
|
Nominal Discharge Current (8/20μs) (In) |
5KA |
|
Max. Discharge Current (8/20μs) (Imax.) |
10KA |
|
Transmission rate (bit / s) |
10M |
|
Insertion loss |
≤0.2dB |
|
Voltage Protection Level (Up) |
≤15V |
|
Response Time |
≤1ns |
|
Input and output impedance |
75Ω |
|
Interface Model |
BNC |
|
Protected Core |
Coaxial type |
|
Protect the port quantity |
8 |
|
Working Environment |
Temperature -40°C~+70°C;Relative humidity<90% |
|
Dimension(L×W×H) |
110×170×40mm |
|
Weight |
0.37kg |
3) Technical Installation:
1. The lightning protection devices are installed between video signal channel and the protected
device, the output termination is connected with the protected equipment.
2. All wirings must be solid and connected by electric.
3. Lightning protect grounding should be consistent with lightning protection regulatory
requirements .The ground wire of SPD should be short and straight.BVR≥2.5 mm2, grounding
resistance: 4Ω.