Power Surge 6 Way socket
KLF-B6-01
1) Product Description:
This product is suitable for lightning protection zone: lightning surge protection of LPZ2 area at
the junction with the LPZ3 (D level) power lines.
It has six international standard jack socket and is designed as modular, is easy to install;
The material of its shell use imported fire-retardant materials, its set of components plug bush
is phosphor bronze, and the products meet international standards and national standards.
With advantage of low residual voltage, fast response and long life, built-in over-current, overload
protection.
It can be inserted 16 kinds of different plugs, full use of every outlet.
It is mainly applied to the lightning protection (over voltage) protection of low-voltage single-
phase AC power supply system electrical and electronic equipment. Such as
telecommunications equipment, computer and network equipment, medical instruments,
precision electronic equipment, household appliances and so on.
2) Technology Parameters:
|
TYPE |
KLF-B6-01 |
|
Protection Class |
D |
|
Nominal Discharge Current (8/20μ s) (In) |
5KA |
|
Max. Discharge Current (8/20μs) (Imax.) |
10KA |
|
Max. Continuous Operating Voltage (Uc) |
275V |
|
Voltage Protection Level( Up) |
≤1.0KV |
|
Response Time |
<25ns |
|
Leakage current |
≤20μA |
|
Maximum load current |
10A |
|
Protection Mode |
L-PE、N-PE |
|
Interface Model |
Six holes |
|
Working Environment |
Temperature:-40°C~+70°C;Relative humidity:<90% |
|
Power line length |
2.4m |
|
Weight |
0.70kg |
3) Product Installation:
1. This SPD is applied to the lightning protection power distribution system for the fourth-class,
it is used in the front of equipment, and its usage is the same as general extension wire.
2. Apply to the lightning protection of electrical equipment, such as: computer centers, control
rooms, information equipment, office electrical equipment, household electrical equipment, high
precision equipment.
3. It is suitable for indoor operation.
4. All wiring must be solid and connect by electric.
5. Lightning proof grounding should be consistent with lightning protection regulatory
requirements; grounding wire should be as thick and short as possible, resistance should be
less than 4O.